FAB Controller Series Specifications
|
|
|
AF-10MR-A / AF-20MR-A
A FAB controller that operates using a AC power source and has relay outputs.
|
Show
Specs Hide
Specs |
| Power Supply |
|
| Allowable range of input voltage |
115V / 120V / 230V / 240VAC |
| VDE0631: |
85V ~ 250VAC |
| IEC1131: |
85V ~ 256VAC |
| Allowable main frequency |
47 ~ 63Hz |
| Real time clock accuracy |
Typical +/-
5s / day |
| Power consumption |
AF-10MR-A ( 3 watts ) |
| |
AF-20MR-A ( 5 watts ) |
| |
|
| Data Capacity Input |
|
| Input Voltage L1 Signal 0 |
0V ~ 40VAC |
| Input Voltage L1 Signal 1 |
79V ~ 256VAC |
| Input Current Signal 1 |
0.24mA typical at 230VAC |
| Delay time from 1 to 0 |
50ms typical |
| Delay time from 0 to 1 |
50ms typical |
| Length of unshielded power line |
100m |
| Data Capacity Output |
Yes |
| Output Type |
Relay Output |
| Electrical Isolation |
Yes |
| Group |
1 |
| Continuous Current |
10A Max |
| Incandescent Lamp Load |
1000 W (230/240VAC) |
| (25,000 switch cycles) |
500 W (115/120VAC) |
Fluorescent Light
w/Electrical Controller |
10 x 58W (230/240VAC) |
| (25,000 Switch cycles) |
|
Fluorescent Light
w/Regular Compensation |
10 x 58W (230/240VAC) |
| (25,000 Switch cycles) |
|
Fluorescent Light
wo/Regular Compensation |
10 x 58W (230/240VAC) |
| (25,000 Switch cycles) |
|
| Short Circuit Protection cos 1 |
Pwr Supply Protection B16 600A |
| Short Circuit Protection cos 0.5 ~ 0.7 |
Pwr Supply Protection B16 900A |
| Output Relay Protection |
20mA Max. Feature B16 |
| |
|
| Switch Frequency |
|
| Mechanical |
10Hz |
| Resistor Load / Lamp Load |
2Hz |
| Induced Load |
0.5Hz |
| |
|
|
|
AF-10MR-D / AF-20MR-D and
AF-10MR-E / AF-20MR-E series
A FAB controller that operates using a DC power source and has relay outputs. The -D models also include analogue inputs.
|
Show
Specs Hide
Specs |
| Power Supply |
|
| Input Voltage |
24VDC |
| Allowable Range |
20.4V ~ 28.8VDC |
24VDC Power consumption
(Full Load) |
1.5W typical |
|
|
| Data Capacity Input |
|
| Rating |
24VDC |
| Signal 0 |
< 5.0 VDC |
| Signal 1 |
> 15.0VDC |
| Input Current Signal 1 |
3mA typical |
|
|
| Delay time from 1 to 0 |
50ms typical |
| Delay time from 0 to 1 |
50ms typical |
|
|
| Length of unshielded power line |
100m |
| Data Capacity Output |
Yes |
| Output Type |
Relay |
| Electrical Isolation |
Yes |
| Group |
1 |
| Continuous Current |
10A Max |
Short Circuit and
Overload Protection |
Yes |
| Incandescent Lamp Load |
1000 W (230/240VAC) |
| (25,000 switch cycles) |
500 W (115/120VAC) |
Fluorescent Light
w/Electrical Controller |
10 x 58W (230/240VAC) |
| (25,000 Switch cycles) |
|
Fluorescent Light
w/Regular Compensation |
10 x 58W (230/240VAC) |
| (25,000 Switch cycles) |
|
Fluorescent Light
wo/Regular Compensation |
10 x 58W (230/240VAC) |
| (25,000 Switch cycles) |
|
| Short Circuit Protection cos 1 |
Pwr Supply Protection B16 600A |
| Short Circuit Protection cos 0.5 ~ 0.7 |
Pwr Supply Protection B16 900A |
| Output Parallel Increased Power |
Not Allowed |
| Output Relay Protection |
20mA Max. Feature B16 |
|
|
| Switch Frequency |
|
| Mechanical |
10Hz |
| Resistor Load / Lamp Load |
2Hz |
| Induced Load |
0.5Hz |
|
|
|
|
AF-10MT-D / AF-20MT-D and
AF-10MT-E / AF-20MT-E series
A FAB controller controller that operates using a DC power source and has
transistor outputs. The -D models also include analogue
inputs.
|
Show
Specs Hide
Specs |
| Power Supply |
AF-xxMT-D/E |
| Input Voltage |
24VDC |
| Allowable Range |
20.4V ~ 28.8VDC |
| 24VDC Power consumption (Full Load) |
1.23A typical |
|
|
| Data Capacity Input |
|
| Rating |
24VDC |
| Signal 0 |
< 5.0 VDC |
| Signal 1 |
> 15.0VDC |
| Input Current Signal 1 |
3mA typical |
|
|
| Delay time from 1 to 0 |
50ms typical |
| Delay time from 0 to 1 |
50ms typical |
|
|
| Length of unshielded power line |
100m |
| Data Capacity Output |
Yes |
| Output Type |
Crystal Tube Current Source |
| Output Voltage |
Power Supply Voltage |
| Output Current |
0.3A Max |
| Continuous Current |
10A Max |
Short Circuit and
Overload Protection |
Yes |
| Short Circuit Current Lim it |
~ 1A |
| Rating Reduction |
Rating not to be reduced in the whole temperature range |
| |
|
|
|
|
|
| |
| Installation Diagrams: |

Click on picture for larger view |
| |
General Specifications:
|
Environmental
|
|
|
|
Item |
Condition |
Basis |
| Operating Temperature Range |
-30º to +70º C |
IEC68-2-1 to IEC68-2-2 |
| Storage Temperature Range |
-30º to +70º C |
IEC68-2-1 to IEC68-2-3 |
| Relative Humidity |
5% to 95% without condensation |
IEC68-30 |
| Atmospheric Pressure |
795 ~ 1080 hpa |
|
| Pollutants |
H2S 1cm3/m3, 4 days
SO2 10cm3/m3, 4 days |
IEC68-2-42
IEC68-2-43 |
| |
|
|
|
Mechanical |
|
|
|
Item |
Condition |
Basis |
| Vibration 2 |
10 ~ 57Hz (constant amplitude 0.15mm) |
IEC68-2-6 |
| |
57 ~ 150Hz (constant acceleration 2g) |
|
| Impact |
18 impacts (semi sine 15g/11ms) |
IEC68-2-27 |
| Fall |
falling height 50mm |
IEC68-2-31 |
| Freely falling body (w/Package) |
1m |
IEC68-2-32 |
| |
|
|
|
Electrical |
|
|
|
Item |
Condition |
Basis |
| Static discharge |
8kv air discharge, 6kv contact discharge |
severe grade 3 |
| Electromagnetic field |
field strength 10V/m |
IEC801-3 |
| Interference suppression |
limitation grade B group 1 |
EN55011 |
| Shock pulse |
2kV for
power line
2kV for signal line |
IEC801-4
severe grade 3 |
| |
|
|
|
IEC/VDE Safety Information |
|
Item |
Condition |
Basis |
| Dielectric strength |
meeting the requirement |
IEC1131 |
back to FAB Controller main page |